5.3.1.2 Regular Maintenance Calibration
Calibrationcanbeperformedduringregularmaintenancevisitsforthepurposeofcomparingthevaluesstoredin
EEPROMtothelatestcurrentcalibrationvaluestodeterminechangesovertime.Thereisnobenefittosavethe
calibrationtoEEPROMifthecompressorhasbeenoperatingnormally.
Acalibrationreportshouldalwaysbecreatedforfuturecomparison.
5.3.1.3 Calibration when Troubleshooting
TroubleshootingproceduresthatrequireabearingcalibrationtobeperformedwillneedtobesavedtoEEPROM.
Clickonthe“SavetoEEPROM”buttonevenifamessageindicatingvaluesareoutofrangeisdisplayed.Ensurethat
“Stored”valuesareupdatedtobeidenticalto“Latest”values.Cyclepowertothecompressorensuringthegreen
LEDontheI/Oboardturnsoff.Thismayneedtoberepeatedmultipletimes.Createacalibrationreportbeforeany
changeismadeandaftereachcalibration.Ensuretheshaftlevitatescorrectlybyclicking“Validate”aftercalibration
valueshavebeensavedtoEEPROM.
NOTE
Thecompressorperformsanautomaticstartupcheckbearingcalibrationafterapowercycle.
5.3.1.4 BMCC Change
IfareplacementBMCCisinstalledinacompressor,acalibrationmustbeperformed,savedtoEEPROM,and
repeatedtomatchtheBMCCtothespecificcompressor.
5.3.2 Performing a Calibration
OnceCalibrationisstarted,theSMTBearingCalibrationToolwillautomaticallychangetheCompressorControl
ModetoCalibrationModeandsendadelevitateshaftsignaltothebearingcontrol.Aftercalibrationiscomplete,the
SMTwillrevertbacktotheoriginalCompressorControlMode.Itisnecessarytoverifythecontrolmodeofthe
compressoraftercompletingthecalibrationprocess.
AmanualvalidationcanbeperformedbyclickingtheValidatebutton.Validationusesthestoredcalibrationvalues
tomomentarilylevitatetheshaftandcomparesthevaluestotolerancelimits.
5.3.2.1 Before Performing a Calibration
l
Interlockmustbeopen
l
RS485orotherexternalcompressorcommunicationconnectionmustbedisconnected
5.3.2.2 Calibration
1. OpentheSMTandconnecttothecompressor.
2. OpentheBearingCalibrationtool.TheBearingCalibrationtooldisplays.RefertoFigure5-2Bearing
CalibrationToolonpage265.
3. ClickontheStartCalibrationbutton.
l
SeethecurrentServiceMonitoringToolsUserManualforfurtherinstructionsonperforminga
calibrationandvalidation.
Page 264 of 294 - M-SV-001-EN Rev. H 1/23/2023

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals