1.8 Electrical Isolation
BeforeservicingtheCompressor,isolatethecompressorpowerbycompletingthefollowingsteps:
DANGER!
l
Thisequipmentcontainshazardousvoltagesthatcancauseseriousinjuryordeath.Onlyqualifiedandtrainedpersonnel
shouldworkonDanfossLLCequipment.
l
Alwayswearappropriately-ratedsafetyequipmentwhenworkingaroundequipmentand/orcomponentsenergizedwith
highvoltage.
l
RemovingtheMainsInputCoverwillexposethetechniciantoahighvoltagehazardofupto632VAC.EnsuretheMains
InputpoweristurnedoffandlockedoutbeforeremovingtheMainsInputCover.
1. TurnofftheMainsInputpowertothecompressor.
2. LockOut/TagOut(LOTO)themainsdisconnecttoensurenoaccidentalorunauthorizedreapplication
oftheMainsInputpowercanoccur.
NOTE
TheMainsInputfast-actingfusesareinstalledinthepowerpanelforallcompressormodelsexcepttheTTS300/TGS230.
3. RemovetheMainsCoveronly.RefertoSection4.1.1MainsInputCoveronpage52.
4. Usinganappropriately-ratedvoltagemeter,confirmtheabsenceofACvoltage.
DANGER!
DonottouchanycomponentswhenremovingtheMainsInputCover.
5. IfACvoltageisnotpresent,reinstalltheMainsInputcoverandwaitatleast20minutesbefore
removingeithertheMainsInputorTopSideCover.IfACvoltagestillexists,gobacktoStep2to
determinewhythecompressorvoltageisnotisolated.
6. RemovetheTopCover,takingparticularcarenottotouchANYcomponentsunderneath.Referto
Section4.1.2TopCoveronpage53.
7. Usinganappropriately-ratedvoltagemeter,checktheDCBusBarsforDCvoltagelevel.Ifthevoltageis
above30voltsdirectcurrent(VDC),waitfive(5)minutesandrecheckuntilvoltageisbelow30VDC.
RefertoFigure1-6DCBusVoltageTestPointsonpage23.
CAUTION
Evenatlowvoltages,cautionshouldbeusedaroundthecapacitorstoavoidquickdischargeevents,whichcanleadtoreducedreliability.
Page 22 of 294 - M-SV-001-EN Rev. H 1/23/2023

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals