EasyManua.ls Logo

Danfoss Turbocor TT Series

Danfoss Turbocor TT Series
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.19.4 SCR Cooling Manifold Specific Installation Steps - TTS300/TGS230
1. ApplyO-LubetotheO-ringsandinstallthemintotheSCRcoolingmanifold.RefertoFigure4-172SCR
ManifoldO-ringInstallation-TTS300/TGS230.
Figure 4-172 SCR Manifold O-ring Installation - TTS300/TGS230
2. InstalltheSCRCoolingManifoldtotheInverterCoolingManifoldusingthetwo(2)M6x20fasteners.
Torqueto7Nm(62in.lb.).
3. SecuretheinsulationontothebacksideoftheSCRCoolingManifold.
4. InstalltheInverter.RefertoSection4.22.6.3CompressorSpecificInverterInstallationSteps-
TTS300/TGS230onpage185.
NOTE
Itisrecommendedthatthenewfastenerssuppliedwiththekitbeusedtoensurepropertorqueisobtained.
5. IftheSCRswereremovedpreviously,installtheSCRstotheSCRcoolingmanifold.TorquetheSCR
fastenersto5Nm(44in.lb.).RefertoSection4.18.3.4SCRInstallation-TTS300/TGS230onpage153.
6. InstalltheDCBusBarandCapacitorAssembly.RefertoSection4.21.4.3DCCapacitorBusBarAssembly
Installation-TTS300/TGS230onpage174.
7. InstalltheTerminalBlockandtorquetheM5x15fastenersto3Nm(27in.lb.).RefertoSection4.11.23-
PhaseMainVoltageInputTerminalBlockRemovalandInstallationonpage102.
8. InstalltheCapacitorCover.RefertoSection4.1.4.1CapacitorCoverRemovalandInstallationonpage
55.
9. Installthefuseassemblies.Torquethesix(6)fastenersto4Nm(35in.lb.).
10. InstallthemainsinputcablestotheTerminalBlockandtorqueto20Nm(15ft.lb.).
11. Leaktestandevacuatethecompressorinaccordancewithstandardindustrypractices.
12. ContinuetoSection4.19.6SCRCoolingManifoldGeneralInstallationStepsonpage162.
4.19.5 SCR Cooling Manifold Specific Installation Steps - TTS/TGS/TTH/TGH (Except TTS300/TGS230)
1. CleantheO-ringgrooveontopoftheInverterCoolingManifoldwithalint-freecloth.
2. ApplyO-LubetoanewInverterHeatSinkO-ringandplaceintheO-ringgroveintheInverterHeatSink
Plateandinstall.RefertoFigure4-173InverterHeatSinkPlateO-ringInstallation-TTS/TGS/TTH/TGH
(ExceptTTS300/TGS230)onpage161.
Page 160 of 294 - M-SV-001-EN Rev. H 1/23/2023

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Related product manuals