Table 5-5 Bearing Fault Types
Bearing Status Description
StartupCalibrationCheckFault AdiscrepancybetweentheBearingStartupcheckandthestoredcalibrationvalueshasbeendetected.
AxialDisplacementFault AxialOrbithasexceededthelimitlongerthanthemaximumtimeallowable.
AxialOvercurrentFault AxialCurrenthasexceededthelimitlongerthanthemaximumtimeallowable.
FrontRadialDisplacementFault FrontRadialOrbithasexceededthelimitlongerthanthemaximumtimeallowable.
FrontRadialXOvercurrentFault FrontRadialXCurrenthasexceededthelimitlongerthanthemaximumtimeallowable.
FrontRadialYOvercurrentFault FrontRadialYCurrenthasexceededthelimitlongerthanthemaximumtimeallowable.
RearRadialDisplacementFault RearRadialOrbithasexceededthelimitlongerthanthemaximumtimeallowable.
RearRadialXOvercurrentFault RearRadialXCurrenthasexceededthelimitlongerthanthemaximumtimeallowable.
RearRadialYOvercurrentFault RearRadialYCurrenthasexceededthelimitlongerthanthemaximumtimeallowable.
5.2 Troubleshooting with the Service Monitoring Tools Software
TheSMTsoftwarepackagecanbeusedtoviewdetailedcompressorinformationforoperationalstatusindications
andtroubleshootingprocedures.PleaserefertotheServiceMonitoringToolsUserManualforthedetailsonhowto
usetheSMTsoftware.
5.2.1 Compressor Fault Troubleshooting
Whentroubleshootingacompressorfault,detailedanalysisofthisdatashouldbemade(inconjunctionwitha
compressorrecordingfile,ifpossible)todeterminethespecificfaultanddeterminetherootcauseoffault
occurrence.
Downloadingfaultandeventlogseverytimeacompressorisvisitedisusefulfordocumentingcompressor
operationalhistory.
FaultandeventhistorycanbeextractedfromthecompressormemoryintheSMTLoggedEventandFaultViewer
tool.SeethelatestServiceMonitoringToolsUserManualforuserinstructions.
ActivecompressorfaultandalarmmessagescanbeviewedintheSMTActiveAlarm/FaultViewertool.Seethelatest
ServiceMonitoringToolsUserManualforuserinstructions.
CompressorAlarmandFaultsettingscanbefoundintheConfigureAlarms/FaultsmenuoptionoftheActive
Alarm/FaultViewertool.
TheCompressor Data RecordingandPlaybacktoolprovidesamethodofreviewingoperationalconditionswithouta
connectiontothecompressor.Italsocreatesafiletoelectronicallytransmitforpeerreview.SeethelatestService
MonitoringToolsUserManualforuseinstructions.
Thefollowingprincipleisappliedwhenhavingbothafaultand/oranalarmlimitastriggers.RefertoFigure5-1
FaultTriggerMethodsonpage255forexplanationsregardingfaultsandalarmsandthetriggermethod
terminologyisused:
l
Instantfaulttriggering(INS)
l
AscendingFaultTriggering(AFT)
l
DescendingFaultTriggering(DFT)
l
RangeFaultTriggering(RFT)
Page 254 of 294 - M-SV-001-EN Rev. H 1/23/2023

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals