4.23.4 Motor Verification
CAUTION
Donotattempttoperformaninsulationtestonacomponentundervacuum.Thiscancauseinsulationbreakdownorfailureduringthe
testingprocess.
4.23.4.1 Stator Insulation Verification
1. IsolatethecompressorpowerasdescribedinSection1.8ElectricalIsolationonpage22.
2. RemovetheSoftStart.RefertoSection4.14.3SoftStartRemovalandInstallationonpage117.
3. RemovetheCopperTubesthatconnectthemotorbusbarstotheInverter.
CAUTION
AfaultyStatorcancausetheInvertertofail.
4. Usingamega-ohmmetersetfor1000VDCmeasurements,connectthered(+)mega-ohmmeterleadto
oneofthethreemotorbusbarsandtheblack(-)mega-ohmmeterleadtothecompressorhousing.
Themeasuredvalueshouldbegreaterthan100mega-ohms.Ifthemeasuredvaluedoesnot
correspondtotheexpectedresistance,thentheStatorinsulationisfaultyandthecompressorneedsto
bereplaced.
5. RepeatStep4fortheremainingtwo(2)motorbusbarstoensureallwindingsareintact.
4.23.4.2 Stator Resistance Verification
ToverifytheStatorresistance,completethefollowingsteps:
1. IsolatethecompressorpowerasdescribedinSection1.8ElectricalIsolationonpage22.
2. RemovetheSoftStart.RefertoSection4.14.3SoftStartRemovalandInstallationonpage117.
3. RemovetheCopperTubesthatconnectthemotorbusbarstotheInverter.
4. Usingamultimetersetforresistancemeasurements,placethered(+)multimeterleadononeofthe
three(3)motorbusbarsandtheblack(-)multimeterleadonanothermotorbusbarandrecordthe
results.Themeasuredvalueshouldbelessthanbutnotzero.Ifthemeasuredvalueis0.or
greaterthan1Ω,thentheStatorwindingisfaultyandthecompressormustbereplaced.
5. RepeatStep4fortheremainingcombinationsofmotorbusbarstoensureallwindingsareintact.
4.23.4.3 Stator Thermistor Resistance Verification
1. IsolatethecompressorpowerasdescribedinSection1.8ElectricalIsolationonpage22.
2. DisconnecttheDCsupplycableharnessfromthemotorthermistorterminals.RefertoFigure4-217
ConnectiontoStatoronpage194.
3. Usingamultimetersetforresistancemeasurements,placethered(+)multimeterleadononemotor
thermistorterminalandtheblack(-)multimeterleadontheothermotorthermistorterminal.The
measuredvalueshouldcorrespondtotheexpectedresistance(150-30at70°F(21°C)outlinedin
Figure4-218StatorThermistorR/TCurveonpage196.Ifthemeasuredvaluedoesnotcorrespondto
theexpectedresistance,thentheStatorthermistorisfaultyandthecompressormustbereplaced.
M-SV-001-EN Rev. H-1/23/2023 Page 195 of 294

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals