6. CleantheO-ringfaceofthesleeveensuringnoscratchesordebrisarepresent.Applyalightamountof
O-ringlubetothefaceofthesleeveandassembletothefitting.Tightenthenutusingtwo(2)
wrenches;one(1)toholdbodyoffittingandone(1)totightenthenut.Thisisdonetopreventover
torqueingthefittinginthecompressorhousing.
Rigid 3/8 inch copper connection - TTS300/TGS230
l
Iftheconnectionis3/8inchrigidcopper,alengthof1/2inchcoppermustbebrazedintothebraze
sleeveasdescribedabove.Atransitionfittingshouldbebrazedtoconnectthe3/8to1/2inch
tubes.FollowtheprocedureasnotedaboveinRigid1/2CopperConnectionsection.
Important
l
Itshouldbenotedthattheinclusionofastrainerwithintheconnectionbodyisintendedasalast
resortbackuponlytopreventingressofdebristhatmayblocksolenoidorificesorrestrictmotor
andpowerelectronicscooling.Itisnotasubstituteforacorrectlysizedfull-flowfilterdrier.Afilter
driermustbeinstalledinallinstances.Ifitisfoundthatafilterdrierisnotinstalled,andthefitting
ischangedduetoafieldreplacementofthecompressor,afilterdriermustbeincludedintheline
modification.
l
Ifitisrequiredtoremovethefittingfromthehousingforanyreason,cleantheO-ring,fittingand
housingthreads,andapplyasmallamountofO-ringlubebeforereassembly.
3.5 Exterior Connection Torque Specifications
Table 3-2 Exterior Connection Torque Specifications
Description Thread Depth (mm) Nm Ft. Lb. In.Lb.
PowerCableNut(excludingTTS300/TGS230compressors) - 21 15 186
InputPressureScrews(TTS300/TGS230compressors) - 20 15 177
MotorCoolingBody,E-housingandlater - 25 18 221
MotorCoolingCompressionNut,E-housingandlater - 11 8 97
GroundPost,TopNut - 10 7 89
GroundPost,Second(Jam)Nut - 7 - 62
GroundPost,LowerNut - 20 15 177
SuctionFlangeFastener 34.5 75 55 664
DischargeFlangeFastener 20 32 24 283
EconomizerFlangeFastener 20 32 24 283
SchraderValve - 15 11 133
BaseMountingBolt 24 22 16 195
CoverFastener - 1.5 - 13
CompressorMountingFastener - 14 10 124
M-SV-001-EN Rev. H-1/23/2023 Page 45 of 294

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals