5.4 SMT Compressor Connection Status Indications
l
Disconnected:noconnectionexistswithacompressororremotecompressorhost
l
ReadytoConnect:aconnectionwitharemotehost(ifapplicable)hasbeenestablished,butno
compressorconnectionhasyetbeenestablished
l
Compressorisstartingup:Thecurrentlyconnectedcompressorisinstartupmode
l
Connected:Therehasbeenestablishedaconnectionwitharemotehost(ifapplicable)anda
connectionwithacompressorhasbeenestablishedandverified
l
Nocompressorfound:Anyserialportsorconnectionshavebeenestablished,butavalid
compressorconnectionwasnotabletobedetected
l
Erroropeningport:Therewasanerroropeningthespecifiedserialport(eithertheportisalreadyin
use,theportnamedoesn’texist,ortherewassomeothererrorattemptingtoopentheserialport)
l
Servernotfound:Couldnotconnecttoremotehost
5.5 System and Compressor Level Troubleshooting
5.5.1 Compressor Voltage Troubleshooting
1. Carefully,removetheMainsInputCover.
2. Verifyallthree(3)phasesofvoltagebeforethemainsfuses.RefertoSection4.11.1.13-PhaseACinput
Verificationonpage100.
l
Ifthenameplateratedvoltageispresent,proceedtoStep3
l
Ifthevoltageis(+/-10%)outsideofthenameplateratedvoltage,restorecorrectvoltage
3. Verifyallthreephasesofvoltageafterthemainsfuses.
l
IfthenameplateratedvoltageispresentproceedtoStep4
l
Ifanyofthethreephasesarenotpresent,isolatecompressorpowerthenreplacethefuses
4. IsolatethecompressorpowerasdescribedintheSection1.8ElectricalIsolationonpage22.
5. Inspectallelectronicsforvisibledamage.
l
Ifnovisibledamageispresent,proceedtoStep6
l
Ifthereisanytypeofvisibledamage,replacethedamagedcomponent(s)
6. VerifyalloftheSoftStartfuses(ClosedToponly).RefertoSection4.14.2.2VerifyingSoftStartFuseson
page116.
l
Ifallofthefusesareokay,proceedtoStep7
l
Ifanyofthefusesareblown,replacethefuse(s)andreviewthecauseoftheblownfuses-Referto
Section5.5.2.6DeterminingtheCauseofBlownSoftStartFuses(Closed-TopSoftStartOnly)on
page272.
7. VerifytheInvertercabletotheInverterconnectorisinstalledcorrectly.
8. VerifytheDC-DCConverterresistances.RefertoSection4.24.2DC-DCConverterVerificationonpage
204.
l
IfDC-DCConverterresistancesarecorrect,proceedtoStep9
l
IfDC-DCConverterresistancesarenotcorrect,replacetheDC-DCConverterthenverifythePWM
andbearings
9. InstalltheDCBustestharness.RefertoSection1.10.1GeneralVerificationandInstallationoftheDC
BusTestHarnessonpage26.
10. DisconnecttheJ2(250VDC)andJ3(24VDC)(PottedDC-DC)orJ4(24VDC)OpenFrameDC-DC)outputs
fromtheDC-DCConverter.
11. InstalltheTopCoverthenre-applythecompressorpower.
M-SV-001-EN Rev. H-1/23/2023 Page 269 of 294

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals