MVX9000 Parameter Listing
MVX9000 User Manual B-7
Parameter Tables
Table B-4: 50 — DRIVE CONTROL (Continued)
Modbus Groups Page # Description Range Default
User
Settings
030BH 50.12 5-34 Acceleration Time 1 0.01 to d 600.0 sec 10.00
030CH 50.13 5-34 Deceleration Time 1 0.01 to d 600.0 sec 10.00
030DH 50.14 5-34 Acceleration Time 2 0.01 to d 600.0 sec 10.00
030EH 50.15 5-35 Deceleration Time 2 0.01 to d 600.0 sec 10.00
030FH 50.16 5-35 Transition Point for
Acceleration 1 to
Acceleration 2
0.0:Disable 0.0
Above min freq.: Enable, 0.0
to 400.0 Hz
0310H 50.17 5-36 Transition Point for
Deceleration 1 to
Deceleration 2
0.0:Disable 0.0
Above min freq.: Enable, 0.0
to 400.0 Hz
0311H 50.18 5-36 Acceleration S-curve 00 to 07 00
0312H 50.19 5-36 Deceleration S-curve 00 to 07 00
0313H 50.20 5-37 Jog Acceleration /
Deceleration Time
0.01 to d 600.0 sec 1.00
0314H 50.21 5-37 Jog Frequency 0.1 to 400.0 Hz 6.0
0315H 50.22 5-37 Reserve Operation
Enable
00: Enable Reverse Operation 00
01: Disable Reverse
Operation
0316H 50.23 5-38 Momentary Power
Loss (Ride Through)
00: Stop operation after
momentary power loss
00
01: Continue operation after
momentary power loss,
speed search from Speed
Reference
02: Continue operation after
momentary power loss,
speed search from Minimum
Speed
0317H 50.24 5-38 Maximum Allowable
Power Loss Time
0.3 to 5.0 sec 2.0
0318H 50.25 5-38 Pause Time after
Momentary Power
Loss
0.3 to 10.0 sec 0.5
0319H 50.26 5-39 Maximum Speed
Search Current Level
30 to 200% 150
031AH 50.27 5-39 Upper Limit of
Output Frequency
0.1 to 400.0 Hz 400.0
031BH 50.28 5-39 Lower Limit of
Output Frequency
0.0 to 400.0 Hz 0.0
031CH 50.29 5-40 Skip Frequency 1 0.0 to 400.0 Hz 0.0
031DH 50.30 5-40 Skip Frequency 2 0.0 to 400.0 Hz 0.0
031EH 50.31 5-40 Skip Frequency 3 0.0 to 400.0 Hz 0.0
031FH 50.32 5-40 Skip Frequency
Bandwidth
0.1 to 20.0 Hz (0.0 = Disable) 0.0
0320H 50.33 5-41 Auto Restart After
Fault
00 to 10 00
0321H 50.34 5-41 PID Set Point
Location
00: Disable
01: Keypad (based on 20.03
setting)
02: AI1 (external 0 – 10V)
03: AI2 (external 4 – 20 mA)
04: PID set point (50.43)
00