QuickstartwithProLinkII
4.ClickRestoreFactoryConguration.
5.ClickOK.
3.4ConfiguretheprimarymAoutputtoreportmassflow
rateinauser-selectedmeasurementunit
ThisprocedureshowsyouhowtoperformthesetasksusingProLinkII.Forallothercongurationtasks,
includingotheroptionsforthemAoutput,seethecongurationsectionsofthismanual.
Note
Thisprocedureassumesthatyouarestartingfromthefactory-defaultconguration.
Procedure
1.StartProLinkIIandconnecttoyourtransmitter.
2.Setthemeasurementunitformassowrate.
a.ChooseProLink→Conguration.
b.IntheCongurationwindow,clicktheFlowtab.
c.SelectameasurementunitfromtheMassFlowUnitslist,thenclickApply.
3.CongurethemAoutput.
a.IntheCongurationwindow,clicktheAnalogOutputtab.
b.SelectMassFlowRatefromthePrimaryVariableIslist.
c.EnterappropriatevaluesforLowerRangeValue(LRV)andUpperRangeValue(URV).
LowerRangeValuespeciesthevalueofMassFlowRatetoberepresentedbyanoutputlevelof
0mAor4mA.
UpperRangeValuespeciesthevalueofMassFlowRatetoberepresentedby
anoutputlevelof20mA.
4.ClickOKtoapplythechangesandclosetheCongurationwindow.
5.(Optional)ChooseProLink→OutputLevelsandobservethemAoutputreading.
Itshouldvarybetween0mAor4mAand20mAaccordingtothemassowrateofyourprocess.
3.5Performalooptest
9739MVDTransmitterProLink→Test→FixMilliamp1
ProLink→Test→FixMilliamp2
ProLink→Test→FixFreqOut
ProLink→Test→FixDiscreteOut
ProLink→Test→ReadDiscreteInput
ProLink→Test→ReadMilliampInput
Alooptestisawaytoverifythatthetransmitterandthereceivingdevicearecommunicatingproperly.A
looptestalsohelpsyouknowwhetheryouneedtotrimmAoutputs.
Alooptestisawaytoverifythatthetransmitterandthereceivingdevicearecommunicatingproperly.
AlooptestalsohelpsyouknowwhetheryouneedtotrimmAoutputs.Performingalooptestisnot
ConfigurationandUseManual
41