QuickstartwiththeFieldCommunicator
4.3.1HARTsecurity
HARTsecuritymaybeenabledonthe9739MVDtransmitter.T ocongurethetransmitterusingHART
protocol,youmustdisableHARTsecurity.
4.3.2Defaultvaluesandranges
DefaultvaluesandrangesforthemostcommonlyusedparametersareprovidedinAppendixA.
4.4ConfiguretheprimarymAoutputtoreportmassflow
rateinauser-selectedmeasurementunit
Note
Thisprocedureassumesthatyouarestartingfromthefactory-defaultconguration.
Procedure
1.MakeaconnectionfromtheFieldCommunicatortoyourtransmitter.
2.NavigatetotheOn-LineMenu.
3.Setthemeasurementunitformassowrate.
a.PressCongure→ManualSetup→Measurements→Flow→MassFlowUnit.
b.Selectthedesiredmeasurementunitfromthelist.
c.PresstheleftarrowuntilyouarereturnedtotheManualSetupmenu.
4.CongurethemAoutput.
a.PressInputs/Outputs→mAOutput1→PrimaryVariable.
b.SelectMassFlowRatefromthelist.
c.PressENTERuntilyouarereturnedtothemAOutput1menu.
d.PressmAOutputSettings.
e.PressPVLRVandenteranappropriatevalueforLowerRangeValue(LRV).
LowerRangeValuespeciesthevalueofMassFlowRatetoberepresentedbyanoutputlevelof
0mAor4mA.
f.PressENTER.
g.PressPVURVandenteranappropriatevalueforUpperRangeValue(LRV).
UpperRangeValuespeciesthevalueofMassFlowRatetoberepresentedbyanoutputlevel
of20mA.
h.PressENTER.
5.(Optional)PressOverview→Shortcuts→Variables→Outputs→Current(mAoutput1)andobservethemA
outputreading.
ConfigurationandUseManual