Configuredeviceoptionsandpreferences
Thisfunctionisaccessedfromthetotalizervalueonthedisplay.Iftheappropriatetotalizerisnot
conguredasadisplayvariable,theoperatorwillnotbeabletoresetit.
6.2.3EnableordisabletheAcknowledgeAllAlarmsdisplaycommand
Display
OFF-LINEMAINT→OFF-LINECONFG→DISPLAY→ALARM
ProLinkII
ProLink→Conguration→Display→DisplayOptions→DisplayAckAllAlarms
FieldCommunicator
Notavailable
Youcancontrolwhetherornottheoperatorwillbeabletouseasinglecommandtoacknowledge
allalarmsfromthedisplay.
Procedure
EnableordisableAcknowledgeAllAlarmsasdesired.
OptionDescription
Enabled(default)Operatorscanuseasingledisplaycommandto
acknowledgeallalarmsatonce.
DisabledOperatorscannotacknowledgeallalarmsatonce.
Theymustacknowledgealarmsindividually.
Note
Toacknowledgealarmsfromthedisplay,theoperatormusthaveaccesstothealarmmenu,whether
AcknowledgeAllAlarmsisenabledordisabled.
6.3Configuresecurityforthedisplaymenus
Display
OFF-LINEMAINT→OFF-LINECONFG→DISPLAY→OFFLN
ProLinkII
ProLink→Conguration→Display→DisplayOptions→DisplayOfineMenu
FieldCommunicator
Notavailable
Youcancontroloperatoraccesstodifferentsectionsofthedisplayoff-linemenu,andyoucancontrol
whetherornotapasswordisrequiredatspecicentrypoints.
Procedure
1.Tocontroloperatoraccesstothemaintenancesectionoftheoff-linemenu,enableordisable
Off-LineMenu.
ConfigurationandUseManual
105