Integratethemeterwiththecontrolsystem
Thedefaultvalueis2.0mA.Therangeis1.0mAto3.6mA.
OptionsformAOutputFaultActionandmAOutputFaultLevel
OptionsformAOutputFaultActionandmAOutputFaultLevelareshowninT able7-4.
Table7-4OptionsformAOutputFaultActionandmAOutputFaultLevel
Code
ProLinkII
FieldCommunica-
tormAOutputFaultLevelmAoutputbehavior
UpscaleUpscale21–24mA
Default:22mA
Goestotheconguredfaultlevel
Downscale(default)Downscale(default)
0.0–3.6mA
Default:2.0mA
Goestotheconguredfaultlevel
InternalZeroIntrnlZeroNotapplicable
GoestothemAoutputlevel
associatedwithaprocessvariable
valueof0(zero),asdeterminedby
LowerRangeValueandUpperRange
Valuesettings
NoneNoneNotapplicable
Tracksdatafortheassigned
processvariable;nofaultaction
IfyousetmAOutputFaultActionorFrequencyOutputFaultActiontoNone,besuretosetDigital
CommunicationsFaultActiontoNone.Ifyoudonot,theoutputwillnotreportactualprocessdata,
andthismayresultinmeasurementerrororunintendedconsequencesforyourprocess.
IfyousetDigitalCommunicationsFaultActiontoNAN,youcannotsetmAOutputFaultActionor
FrequencyOutputFaultActiontoNone.Ifyoutrytodothis,thetransmitterwillnotacceptthe
conguration.
7.2Configurethefrequencyoutput
Display
OFF-LINEMAINT→OFF-LINECONFG→IO→FO
ProLinkII
ProLink→Conguration→Frequency
FieldCommunicatorCongure→ManualSetup→Inputs/Outputs→FrequencyOutput
Thefrequencyoutputisusedtoreportaprocessvariable.Thefrequencyoutputparameterscontrol
howtheprocessvariableisreported.
124MicroMotion9739MVDTransmitters