System integration Proline Promag W 400 EtherNet/IP
72 Endress+Hauser
Configuration 5: Exclusive Owner Multicast
Input Assembly Fix Instance Size [byte] min. RPI (ms)
Input Assembly Configurable Configuration 0 x 69
Output Assembly Fix O → T Configuration 0 x 66 64 5
Input Assembly Fix T → O Configuration 0 x 64 44 5
Configuration 6: Input Only Multicast
Input Assembly Fix Instance Size [byte] min. RPI (ms)
Input Assembly Configurable Configuration 0 x 69
Output Assembly Fix O → T Configuration 0 x C7
Input Assembly Fix T → O Configuration 0 x 65 44 5
Configuration 7: Exclusive Owner Multicast
Input Assembly Configurable Instance Size [byte] min. RPI (ms)
Input Assembly Configurable Configuration 0 x 69
Output Assembly Fix O → T Configuration 0 x 66 64 5
Input Assembly Fix T → O Configuration 0 x 64 88 5
Configuration 8: Input Only Multicast
Input Assembly Configurable Instance Size [byte] min. RPI (ms)
Input Assembly Configurable Configuration 0 x 69
Output Assembly Fix O → T Configuration 0 x C7
Input Assembly Fix T → O Configuration 0 x 65 88 5
Permanently assigned input group
Input Assembly Fix (Assem100) 44 Byte
Name Description Byte
Input Assembly Fix 1. File header (not visible) 1 to 4
2. Current diagnosis
1)
5 to 8
3. Mass flow 9 to 12
4. Volume flow 13 to 16
5. Corrected volume flow 17 to 20
6. Temperature 21 to 24
7. Density 25 to 28
8. Reference density 29 to 32
9. Totalizer 1 33 to 36