7 Block OUTPUTS Device Functions Proline Promass 83 MODBUS RS485
100 Endress+Hauser
7.3.5 Switching response of the relay output
Function State Relay coil
Contact*
NC NO
ON (operation) System in measuring mode
energized
A0001239 A0001237
System not in measuring mode
(power supply failed)
de-
energized
A0001240 A0001238
Fault message System OK
energized
A0001239 A0001237
(System or process error)
Fault → Response to error,
outputs /
Inputs and totalizers
de-
energized
A0001240 A0001238
Notice message System OK
energized
A0001239 A0001237
(System or process error)
Fault → Continuation of
measuring
de-
energized
A0001240 A0001238
Fault message
or
Notice message
System OK
energized
A0001239 A0001237
(System or process error)
Fault → Response to error
or
Note → Continuation of
measuring
de-
energized
A0001240 A0001238
Empty pipe
detection (EPD)
Measuring tube full
energized
A0001239 A0001237
Measuring tube partially filled
/empty measuring tube
de-
energized
A0001240 A0001238