Device Functions Proline Promass 83 MODBUS RS485 7 Block OUTPUTS
Endress+Hauser 93
7.3 Group RELAY OUTPUT (1 to 2)
7.3.1 Function group CONFIGURATION
OUTPUTS E CURRENT OUTPUT 1 EAA
PULSE/FREQ. OUTPUT 1 ECA
RELAY OUTPUT 1 EGA CONFIGURATION 470
RELAY OUTPUT 2 EGB CONFIGURATION 470
Function description
OUTPUTS RELAY OUTPUT (1 to 2) CONFIGURATION
ASSIGN RELAY
MODBUS register:
Relay output 1
Relay output 2
Data type:
Access:
4700
3801
4001
Integer
read/write
Use this function to assign a switching function to the relay output.
Options: (standard)
0 = OFF
1 = ON (operation)
2 = FAULT MESSAGE
3 = NOTICE MESSAGE
4 = FAULT MESSAGE or NOTICE MESSAGE
5 = EPD (empty pipe detection, only if active)
6 = FLOW DIRECTION
7 = MASS FLOW LIMIT VALUE
8 = VOLUME FLOW LIMIT VALUE
14 = CORRECTED VOLUME FLOW LIMIT VALUE
15 = DENSITY LIMIT VALUE
16 = REFERENCE DENSITY LIMIT VALUE
17 = TEMPERATURE LIMIT VALUE
19 = TOTALIZER 1 LIMIT VALUE
20 = TOTALIZER 2 LIMIT VALUE
21 = TOTALIZER 3 LIMIT VALUE
Advanced selection: with the optional SW package BATCHING
22 = BATCH VALVE 1 (e.g. to control valve 1)
23 = BATCH VALVE 2 (e.g. to control valve 2)
25 = BATCH RUNNING
26 = > BATCH TIME
27 = >< BATCH QUANTITIES (< min. / > max. batching quantity)
28 = PROGRESS NOTE (batching end approaching)
! Note!
The batching valves defined in the function BATCH STAGES (7208) are the
only available selection (max. 2).
The only options available are the monitoring functions (7240 to 7243) which
have a value not equal to zero (max. 2).
Advanced selection: with the optional SW package CONCENTRATION
30 = LIMIT TARGET MASS FLOW
31 = LIMIT TARGET % MASS PROPORTION FLOW
32 = LIMIT TARGET VOLUME FLOW
33 = LIMIT TARGET % VOLUME PROPORTION FLOW
34 = LIMIT TARGET CORRECTED VOLUME FLOW
35 = LIMIT CARRIER MASS FLOW
36 = LIMIT CARRIER % MASS PROPORTION FLOW
37 = LIMIT CARRIER VOLUME FLOW
38 = LIMIT CARRIER % VOLUME PROPORTION FLOW
39 = LIMIT CARRIER CORRECTED VOLUME FLOW
40 = LIMIT % BLACK LIQUOR
41 = LIMIT °BAUME > 1
42 = LIMIT °BAUME < 1
43 = LIMIT °API
44 = LIMIT °PLATO
45 = LIMIT °BALLING
46 = LIMIT °BRIX
47 = LIMIT OTHER (_ _ _ _ flexible concentration)
(continued on next page)