Device Functions Proline Promass 83 MODBUS RS485 7 Block OUTPUTS
Endress+Hauser 67
7.1.2 Function group OPERATION
7.1.3 Function group INFORMATION
OUTPUTS E → CURRENT OUTPUT 1 EAA → CONFIGURATION 400
→
OPERATION 404
Function description
OUTPUTS → CURRENT OUTPUT 1 → OPERATION
ACTUAL CURRENT
MODBUS register:
Data type:
Access:
4040
5811
Float
read
Use this function to view the computed actual value of the output current.
Display: 0.00 to 25.00 mA
SIMULATION
CURRENT
MODBUS register:
Data type:
Access:
4041
5813
Integer
read/write
Activates simulation of the current output.
Options:
0 = OFF
1 = ON
Factory setting: OFF
! Note!
• If simulation is active, the “SIMULATION CURRENT OUTPUT” message is
displayed.
• The measuring device continues to measure while simulation is in progress, i.e.
the current measured values are output correctly via the other outputs.
" Caution!
The setting is not saved in the event of a power failure.
VALUE
SIMULATION
CURRENT
MODBUS register:
Data type:
Access:
4042
5814
Float
read/write
! Note!
The function is not visible unless the function SIMULATION CURRENT (4041) is
active.
For defining a freely selectable value (e.g. 12 mA) to be output at the current
output. This value is used to test downstream devices and the measuring device
itself.
User input: 0.00 to 25.00 mA
Factory setting: 0.00 mA
" Caution!
The setting is not saved in the event of a power failure.
OUTPUTS E → CURRENT OUTPUT 1 EAA → CONFIGURATION 400
→
OPERATION 404
→
INFORMATION 408
Function description
OUTPUTS → CURRENT OUTPUT 1 → INFORMATION
TERMINAL
NUMBER
MODBUS register:
Data type:
Access:
4080
5816
Integer
read
Displays the:
• Numbers of the terminals used by the current output (in the connection
compartment)
•Polarity
Display:
3 = 20 (+) / 21 (–)