7 Block OUTPUTS Device Functions Proline Promass 83 MODBUS RS485
66 Endress+Hauser
FAILSAFE MODE
MODBUS register:
Data type:
Access:
4006
5810
Integer
read/write
For safety reasons it is advisable to ensure that the current output assumes a
predefined state in the event of a fault. The setting you select here affects only the
current output. It has no effect on other outputs and the display (e.g. totalizers).
Options:
0 = MIN. CURRENT
The current output adopts the value of the lower signal on alarm level (as defined
in the function CURRENT SPAN (4001), see Page 60).
1 = MAX. CURRENT
The current output adopts the value of the upper signal on alarm level (as defined
in the function CURRENT SPAN (4001), see Page 60).
2 = HOLD VALUE (not recommended)
Measuring value output is based on the last measuring value saved before the
error occurred .
3 = ACTUAL VALUE
Measured value output is based on the current flow measurement.
The fault is ignored.
Factory setting: MIN. CURRENT
Function description
OUTPUTS CURRENT OUTPUT 1 CONFIGURATION