Device Functions Proline Promass 83 MODBUS RS485 8 Block INPUTS
Endress+Hauser 103
8.1 Group STATUS INPUT
8.1.1 Function group CONFIGURATION
INPUTS F STATUS INPUT FAA CONFIGURATION 500
Function description
INPUTS STATUS INPUT CONFIGURATION
ASSIGN STATUS
INPUT
MODBUS register:
Data type:
Access:
5000
4301
Integer
read/write
Use this function to assign a switching function to the status input.
Options:
0 = OFF
1 = RESET TOTALIZER 1
2 = RESET TOTALIZER 2
3 = RESET TOTALIZER 3
4 = RESET ALL TOTALIZERS
5 = POSITIVE ZERO RETURN
8 = ZEROPOINT ADJUST
Advanced selection: with the optional SW package BATCHING:
9 = RUN BATCHING (start/stop)
10 = HOLD BATCHING (stop/continue)
11 = RESET BATCH SUM (resetting total quantity / total quantity totalizers)
27 = RESET TOTALIZER 3 & START BATCHING (reset totalizer 3, followed by
start)
" Caution!
If there is an input pulse during a running batching process, the batching process
is aborted immediately. Totalizer 3 is not reset however. This makes it possible to
read out partial filling correctly.
Advanced selection: with the optional SW package ADVANCED DIAGNOSIS
22 = ACQUISITION
! Note!
ACQUISITION is not available unless the MANUELL setting is selected in the
ACQUISITION MODE function (7410).
Factory setting: OFF
" Caution!
POSITIVE ZERO RETURN is active as long as the level is available at the status
input (continuous signal). All other assignments react to a change in level (pulse)
at the status input.
ACTIVE LEVEL
MODBUS register:
Data type:
Access:
5001
4302
Integer
read/write
Use this function to define whether the assigned function (see function ASSIGN
STATUS INPUT(5000)) is released when the signal level is present (HIGH) or not
present (LOW).
Options:
1 = HIGH
0 = LOW
Factory setting: HIGH
MINIMUM PULSE
WIDTH
MODBUS register:
Data type:
Access:
5002
4303
Float
read/write
Use this function to define a minimum pulse width which the input pulse must
achieve in order to trigger the selected switching function, (see function ASSIGN
STATUS INPUT (5000)).
User input: 20 to 100 ms
Factory setting: 50 ms