Device Functions Proline Promass 83 MODBUS RS485 11 Block SUPERVISION
Endress+Hauser 169
11.1.2 Function group OPERATION
SUPERVISION J SYSTEM JAA CONFIGURATION 800
OPERATION 804
Function description
SUPERVISION SYSTEM OPERATION
ACTUAL SYSTEM
CONDITION
MODBUS register:
Data type:
Access:
MODBUS register:
Data type:
Access:
8040
6859
Integer
read
6821
String (18)
read
Displays the present system condition.
Display:
1 = “SYSTEM OK”
or
The fault / notice message with the highest priority.
! Note!
More information can be found in Operating Instructions BA107D under the
keyword “System or process error messages”.
PREVIOUS SYSTEM
CONDITIONS
MODBUS register:
Data type:
Access:
8041
See Note
Integer
read
Use this function to view the sixteen most recent fault and notice messages since
measuring last started.
Display: The 16 most recent fault or notice messages.
! Note for MODBUS!
The various previous system conditions are available via the following MOBBUS
registers (data MODBUS register Integer/String):
Fault/notice message 1 = MODBUS register 6860
Fault/notice message 2 = MODBUS register 6861
Fault/notice message 3 = MODBUS register 6862
Fault/notice message 4 = MODBUS register 6863
Fault/notice message 5 = MODBUS register 6864
Fault/notice message 6 = MODBUS register 6865
Fault/notice message 7 = MODBUS register 6866
Fault/notice message 8 = MODBUS register 6867
Fault/notice message 9 = MODBUS register 6868
Fault/notice message 10 = MODBUS register 6869
Fault/notice message 11 = MODBUS register 6870
Fault/notice message 12 = MODBUS register 6871
Fault/notice message 13 = MODBUS register 6872
Fault/notice message 14 = MODBUS register 6873
Fault/notice message 15 = MODBUS register 6874
Fault/notice message 16 = MODBUS register 6875
! Note!
More information can be found in Operating Instructions BA107D under the
keyword “System or process error messages”.
SIMULATION
FAILSAFE MODE
MODBUS register:
Data type:
Access:
8042
6812
Integer
read/write
Use this function to set all inputs, outputs and totalizers to their defined failsafe
modes, in order to check whether they respond correctly. During this time, the
message “SIMULATION FAILSAFE MODE” appears on the display.
Options:
0 = OFF
1 = ON
Factory setting: OFF