6 Block TOTALIZER Device Functions Proline Promass 83 MODBUS RS485
56 Endress+Hauser
6.1.2 Function group OPERATION
TOTALIZER D TOTALIZER 1 DAA CONFIGURATION 300
OPERATION 304
TOTALIZER 2 DAB CONFIGURATION 300
OPERATION 304
TOTALIZER 3 DAC CONFIGURATION 300
OPERATION 304
Function description
TOTALIZER TOTALIZER (1 to 3) OPERATION
! Note!
The function descriptions below apply to totalizers 1 to 3; the totalizers are independently configurable.
SUM
MODBUS register:
Totalizer 1
Totalizer 2
Totalizer 3
Data type:
Access:
3040
2610
259
261
2810
3010
Float
read
Displays the total for the totalizer's measured variable aggregated since measuring
began. The value can be positive or negative, depending on the setting selected in
the function “TOTALIZER MODE” (3002), and the direction of flow.
Display: max. 7-digit floating-point number, including sign and unit
(e.g. 15467.04 m
3
; 4925.631 kg)
! Note!
The effect of the setting in the “TOTALIZER MODE” function (see Page 55) is
as follows:
If the setting is “BALANCE”, the totalizer balances flow in the positive and
negative directions.
If the setting is “FORWARD”, the totalizer registers only flow in the positive
direction.
If the setting is “REVERSE”, the totalizer registers only flow in the negative
direction.
The totalizer's response to faults is defined in the “FAILSAFE ALL
TOTALIZERS” function (3801), (see Page 57).
OVERFLOW
MODBUS register:
Totalizer 1
Totalizer 2
Totalizer 3
Data type:
Access:
3041
2612
2812
3012
Float
read
Displays the total for the totalizer's overflow aggregated since measuring began.
Total flow quantity is represented by a floating-point number consisting of max. 7
digits. You can use this function to view higher numerical values (>9,999,999) as
overflows. The effective quantity is thus the total of OVERFLOW plus the value
returned by the SUM function.
Example:
Reading for 2 overflows: 2 E7 kg (= 20,000,000 kg).
The value displayed in the function SUM = 196,845.7 kg
Effective total quantity = 20,196,845.7 kg
Display: integer with exponent, including sign and unit,
e.g. 2E7 kg