Device Functions Proline Promass 83 MODBUS RS485 6 Block TOTALIZER
Endress+Hauser 55
TOTALIZER MODE
MODBUS register:
Totalizer 1
Totalizer 2
Totalizer 3
Data type:
Access:
3002
2605
2805
3005
Integer
read/write
For selecting how the totalizer should operate.
Options:
0 = BALANCE
Positive and negative flow components. The positive and negative flow
components are balanced. In other words, net flow in the flow direction is
registered.
1 = FORWARD
Only positive flow components
2 = REVERSE
Only negative flow components
Factory setting:
Totalizer 1 = BALANCE
Totalizer 2 = FORWARD
Totalizer 3 = REVERSE
RESET TOTALIZER
MODBUS register:
Totalizer 1
Totalizer 2
Totalizer 3
Data type:
Access:
3003
2608
2808
3008
Integer
read/write
Resets the total and the overflow of the totalizer to zero.
Options:
0 = NO
1 = YES
Factory setting:
NO
! Note!
If the device is equipped with a status input, with the appropriate configuration a
reset for each individual totalizer can also be triggered by a pulse (see the function
ASSIGN STATUS INPUT (5000) on Page 103).
Function description
TOTALIZER → TOTALIZER (1 to 3) → CONFIGURATION