Device Functions Proline Promass 83 MODBUS RS485 9 Block BASIC FUNCTION
Endress+Hauser 117
9.2.5 Function group PRESSURE CORRECTION
BASIC FUNCTION G → MODBUS RS485 GDA
→
PROCESS PARAMETER GIA → CONFIGURATION 640
→
EPD PARAMETER 642
→
REFERENCE PARAMETER 646
→
ADJUSTMENT 648
→
PRESSURE CORRECTION 650
Function description
BASIC FUNCTION → PROCESS PARAMETER → PRESSURE CORRECTION
PRESSURE MODE
MODBUS register:
Data type:
Access:
6500
5184
Integer
read/write
Use this function to configure an automatic pressure correction.
In this way, the effect of a pressure deviation between the calibration and process
pressures on the measured error for mass flow is compensated for, (see also
Operating Instructions BA107D, “Measuring accuracy” Chapter).
Options:
0 = OFF
1 = FIX (a fixed process pressure for pressure correction is specified).
Factory setting: OFF
PRESSURE
MODBUS register:
Data type:
Access:
6501
5185
Float
read/write
! Note!
Function is not available unless the FIX setting was selected in the PRESSURE
MODE function (6500).
Use this function to enter the value for the process pressure which should be used
during pressure correction.
User input: 7-digit floating-point number
Factory setting: 0 bar g
! Note!
The appropriate unit is taken from the function group SYSTEM UNITS
(see Page 15).