10 Block SPECIAL FUNCTION Device Functions Proline Promass 83 MODBUS RS485
136 Endress+Hauser
AVERAGING DRIP
MODBUS register:
Data type:
Access:
7207
See Note
Float
read/write
! Note!
Function is only available if MODE 1 or MODE 2 is selected in the function
COMPENSATION MODE (7205).
For specifying the number of after run quantities (cycles) which are included in
calculating the batching compensation mode, MODE 1 or MODE 2.
! Note!
The value entered in this function influences the measuring system reaction time.
! Note for MODBUS!
The MOBBUS register depends on the option selected in the function BATCH
SELECTOR (7200):
BATCH # 1 = MODBUS register 6368
BATCH # 2 = MODBUS register 6370
BATCH # 3 = MODBUS register 6372
BATCH # 4 = MODBUS register 6374
BATCH # 5 = MODBUS register 6376
BATCH # 6 = MODBUS register 6378
If you specify:
a small calculation depth (low value entered) = measuring system reacts
quickly to differing amount of after run quantities.
a large calculation depth (high value entered) = measuring system reacts slowly
to changing after run quantities.
User input: 0 to 100
Factory setting:: 0 [cycles]
BATCH STAGES
MODBUS register:
Data type:
Access:
7208
See Note
Integer
read/write
For selecting the number of batching stages. Batching can be carried out in several
stages, e.g. 2-stage batching with fast and precise batching.
Options:
0 = 1-stage (1 valve or 1-stage batching)
1 = 2-stage (2 valves or 2-stage batching)
Factory setting: 1-stage (1 valve or 1-stage batching)
! Note!
The batching stage selection (number of valves) is directly dependent on the
configuration of the outputs. For 2-stage batching two relay outputs must be
available in the measuring device.
The functions available in the function group VALVE PARAMETER (Page 138)
are dependent on the number of batching stages (number of valves) selected in
this function.
! Note for MODBUS!
The MOBBUS register depends on the option selected in the function BATCH
SELECTOR (7200):
BATCH # 1 = MODBUS register 6380
BATCH # 2 = MODBUS register 6381
BATCH # 3 = MODBUS register 6382
BATCH # 4 = MODBUS register 6383
BATCH # 5 = MODBUS register 6384
BATCH # 6 = MODBUS register 6385
Function description
SPECIAL FUNCTION BATCHING FUNCTION CONFIGURATION

Table of Contents