Device Functions Proline Promass 83 MODBUS RS485 10 Block SPECIAL FUNCTION
Endress+Hauser 137
INPUT FORMAT
MODBUS register:
Offset address:
Data type:
Access:
Storage class:
7209
See Note
See Note
Integer
read/write
Volatile
Use this function to define the entry format of the quantities for the switch points
of the valves.
Options:
0 = VALUE-INPUT (e.g. 10 [unit])
1 = %-INPUT (e.g. 80 [%])
Factory setting: VALUE-INPUT
! Note!
The entry format selected in this function is also used in the function groups
VALVE PARAMETER (Page 138) and SUPERVISION (Page 143).
! Note for MODBUS!
The MOBBUS register depends on the option selected in the function BATCH
SELECTOR (7200):
BATCH # 1 = MODBUS register 6386
BATCH # 2 = MODBUS register 6387
BATCH # 3 = MODBUS register 6388
BATCH # 4 = MODBUS register 6389
BATCH # 5 = MODBUS register 6390
BATCH # 6 = MODBUS register 6391
Function description
SPECIAL FUNCTION BATCHING FUNCTION CONFIGURATION