Device Functions Proline Promass 83 MODBUS RS485 10 Block SPECIAL FUNCTION
Endress+Hauser 145
PROGRESS NOTE
MODBUS register:
Data type:
Access:
7243
See Note
Float
read/write
For specifying the batching quantity at which a message should be generated.
When the specified batching quantity is achieved, the message is generated and
signaled via the output. The quantity value is entered as a % or as an absolute
value, depending on the option in the function INPUT FORMAT (7209).
Application:For longer batching processes when preparing or taking measures
related to production (e.g. preparing to replace container, etc.).
User input: 0 to max. value or 0 to 100% (related to the batching quantity)
Factory setting: 0 [unit] (= deactivated)
" Caution!
When the batching quantity is adjusted (reduced/increased), (see function
BATCH QUANTITY (7203) on Page 132), there is no automatic adjustment,
i.e. this value must be determined again and reentered, (see also notice message
# 473 in the Operating Instructions BA107D).
! Note!
The function is not active if you enter 0 (factory setting).
This function can be output via the switch output.
The batching progress message remains active until batching ends.
! Note for MODBUS!
Depends on the option selected in the function BATCH SELECTOR (7200):
BATCH # 1 = MODBUS register 8099
BATCH # 2 = MODBUS register 8101
BATCH # 3 = MODBUS register 8103
BATCH # 4 = MODBUS register 8105
BATCH # 5 = MODBUS register 8107
BATCH # 6 = MODBUS register 8109
MAX. FLOW
VALUE
MODBUS register:
Data type:
Access:
7244
See Note
Float
read/write
For specifying a maximum flow value. The batching process is aborted and all the
valves are closed if the specified flow value is overshot.
Application:
This function can be used for safety reasons, for example, to ensure all batching
valves close in the event of a system fault.
User input: 5-digit floating-point number
Factory setting: 0 [unit] (= deactivated)
! Note!
The appropriate unit is taken depending on the process variable selected in the
parameter ASSIGN BATCH VARIABLE (7202) and the unit configured in the
group SYSTEM UNITS.
The function is not active if you enter 0 (factory setting).
If the batching process is aborted because the specified flow value was
overshot, the parameter BATCH COUNTER (7263) is not incremented.
The error message #474 > MAX. FLOW is output if the maximum flow is
overshot.
This fault message can be acknowledged prematurely:
By modifying a batching function.
By selecting RESET in the “BATCH PROCEDURE” parameter
! Note for MODBUS!
Depends on the option selected in the function BATCH SELECTOR (7200):
BATCH # 1 = MODBUS register 8111
BATCH # 2 = MODBUS register 8113
BATCH # 3 = MODBUS register 8115
BATCH # 4 = MODBUS register 8117
BATCH # 5 = MODBUS register 8119
BATCH # 6 = MODBUS register 8121
Function description
SPECIAL FUNCTION BATCHING FUNCTION SUPERVISION