Device Functions Proline Promass 83 MODBUS RS485 10 Block SPECIAL FUNCTION
Endress+Hauser 147
BATCH COUNTER
MODBUS register:
Data type:
Access:
7263
6397
Float
read
Displays the number of batchings carried out.
Display: max. 7-digit floating-point number
Factory setting: 0
! Note!
The batching quantity totalizer can be reset to 0 via the function RESET
SUM/COUNTER (7265).
This function is reset to 0 (zero) if a different batching specification is selected
in the function BATCH SELECTOR (7200).
BATCH SUM
MODBUS register:
Data type:
Access:
7264
6399
Float
read
Displays the effective overall total of all the batchings carried out.
Display: max. 7-digit floating-point number [unit]
Factory setting: 0 [unit]
! Note!
E.g. in 2-stage batching the effective overall total is calculated from the coarse
batching quantity, fine batching quantity and after run quantity.
The total batching quantity can be reset to 0 via the function RESET
SUM/COUNTER (7265).
This function is reset to 0 (zero) if a different batching specification is selected
in the function BATCH SELECTOR (7200).
RESET
SUM/COUNTER
MODBUS register:
Data type:
Access:
7265
6401
Integer
read/write
Resets the batching quantity counter and the total batching quantity to 0.
Options:
0 = NO
1 = YES
Factory setting: NO
! Note!
The batch counter and the batch sum can also be reset via the batching menu
(information line on the local display) .
Function description
SPECIAL FUNCTION BATCHING FUNCTION OPERATION