9 Block BASIC FUNCTION Device Functions Proline Promass 83 MODBUS RS485
108 Endress+Hauser
BYTE ORDER
MODBUS register:
Data type:
Access:
6305
4915
Integer
read/write
For selecting the byte transmission sequence for the Integer, Float and String data
types.
Options:
0 = 0-1-2-3
1 = 3-2-1-0
2 = 2-3-0-1
3 = 1-0-3-2
Factory setting: 1-0-3-2
! Note!
The transmission sequence must suit the MODBUS master.
More information can be found in Operating Instructions BA107D under the
keyword “Byte transmission sequence”.
DELAY TELEGRAM
REPLY
MODBUS register:
Data type:
Access:
6306
4916
Float
read/write
For entering a delay time after which the measuring device replies to the request
telegram of the MODBUS master. This allows communication to be adapted to
slow MODBUS RS485 masters.
User input: 0 to 100 ms
Factory setting: 10 ms
WRITE
PROTECTION
MODBUS register:
Data type:
Access:
6307
4918
Integer
read
Indicates whether write access to the measuring device is possible via local
operation or MODBUS RS485.
Display:
0 = OFF (write access via MODBUS possible)
1 = ON (write access via MODBUS blocked)
Factory setting: OFF
! Note!
Hardware write protection is activated and deactivated by means of a jumper on
the I/O module (see Operating Instructions BA107D).
SCAN LIST
REGISTER 1 to 16
MODBUS register:
SCAN LIST REG. 1
SCAN LIST REG. 2
SCAN LIST REG. 3
SCAN LIST REG. 4
SCAN LIST REG. 5
SCAN LIST REG. 6
SCAN LIST REG. 7
SCAN LIST REG. 8
SCAN LIST REG. 9
SCAN LIST REG. 10
SCAN LIST REG. 11
SCAN LIST REG. 12
SCAN LIST REG. 13
SCAN LIST REG. 14
SCAN LIST REG. 15
SCAN LIST REG. 16
Data type:
Access:
6308
5001
5002
5003
5004
5005
5006
5007
5008
5009
5010
5011
5012
5013
5014
5015
5016
Integer
read/write
By entering the register address, up to 16 device parameters can be grouped in the
auto-scan buffer where they are assigned to the scan list registers 1 to 16. The
data of the device parameters assigned here are read out via the register addresses
5051 to 5081.
User input: 0 to 9999
Factory setting: 0
! Note!
More detailed information and examples of using the auto-scan buffer are
provided in Operating Instructions BA107D.
Function description
BASIC FUNCTION MODBUS RS485 CONFIGURATION