5 Block USER INTERFACE Device Functions Proline Promass 83 MODBUS RS485
48 Endress+Hauser
ASSIGN
(continued)
2600 Advanced selection: with the optional SW package CONCENTRATION
61 = TARGET MASS FLOW
62 = % TARGET MASS FLOW
63 = TARGET VOLUME FLOW
64 = % TARGET VOLUME FLOW
65 = CORRECTED TARGET VOLUME FLOW
66 = CARRIER MASS FLOW
67 = % CARRIER MASS FLOW
68 = CARRIER VOLUME FLOW
69 = % CARRIER VOLUME FLOW
70 = CORRECTED CARRIER VOLUME FLOW
71 = % BLACK LIQUOR
72 = ° BAUME
74 = ° API
75 = ° PLATO
76 = ° BALLING
77 = ° BRIX
78 = OTHER (_ _ _ _ flexible concentration)
Advanced selection: with the optional SW package ADVANCED DIAGNOSIS
79 = MASS FLOW DEVIATION
80 = DENSITY DEVIATION
81 = REFERENCE DENSITY DEVIATION
82 = TEMPERATURE DEVIATION
83 = TUBE DAMPING DEVIATION
84 = ELECTRODYNAMIC SENSOR DEVIATION
96 = OPERATING FREQUENCY FLUCTUATION DEVIATION
97 = TUBE DAMPING FLUCTUATION DEVIATION
100% VALUE
MODBUS register:
Data type:
Access:
2601
2539
Float
read/write
! Note!
Function is not available unless one of the following was selected in the ASSIGN
function (2600):
MASS FLOW IN %
VOLUME FLOW IN %
CORRECTED VOLUME FLOW IN %
MASS FLOW BARGRAPH IN %
VOLUME FLOW BARGRAPH IN %
CORRECTED VOLUME FLOW BARGRAPH IN %
For specifying the flow value to be shown on the display as the 100% value.
User input: 5-digit floating-point number
Factory setting: 10 kg/s, 10 l/s or 10 Nl/s
FORMAT
MODBUS register:
Data type:
Access:
2602
2538
Integer
read/write
For selecting the maximum number of places after the decimal point to be
displayed for the display value.
Options:
0 = XXXXX
1 = XXXX.X
2 = XXX.XX
3 = XX.XXX
4 = X.XXXX
Factory setting:
X.XXXX
! Note!
Note that this setting only affects the reading as it appears on the display, it has
no influence on the accuracy of the system's calculations.
The places after the decimal point as computed by the measuring device cannot
always be displayed, depending on this setting and the engineering unit. In
such instances an arrow appears on the display between the measuring value
and the engineering unit (e.g. 1.2 kg/h), indicating that the measuring
system is computing with more decimal places than can be shown on the
display.
Function description
USER INTERFACE INFORMATION LINE CONFIGURATION