7 Block OUTPUTS Device Functions Proline Promass 83 MODBUS RS485
88 Endress+Hauser
MEASURING
MODE
MODBUS register:
Data type:
Access:
4246
3245
Integer
read/write
! Note!
Function is not available unless STATUS was selected in the OPERATION MODE
function (4200) and the status output was assigned a limit value.
Use this function to define the measuring mode for the status output.
Options:
0 = STANDARD
The status output signal switches at the defined switch points.
1 = SYMMETRY
The status output signal switches at the defined switch points, irrespective of the
sign. If you define a switch point with a positive sign, the status output signal
switches as soon as the value is reached in the negative direction (negative sign),
(see illustration).
Factory setting: STANDARD
A0001247
Fig. 30 : Example for the SYMMETRY measuring mode
Switch-on point Q = 4
Switch-off point Q = 10
m = Status output switched on (conductive)
n = Status output switched off (nonconductive)
! Note!
SYMMETRY cannot be selected unless the values in the ON-VALUE (4242)
and OFF-VALUE (4244) functions have the same sign or one of the values is
zero.
If the values have different signs, SYMMETRY cannot be selected and an
“ASSIGNMENT NOT POSSIBLE” message is displayed.
TIME CONSTANT
MODBUS register:
Data type:
Access:
4247
3246
Float
read/write
! Note!
Function is not available unless the STATUS setting was selected in the
OPERATION MODE function (4200).
Entering a time constant defines how the measuring signal reacts to severely
fluctuating measured variables, either very quickly (enter a low time constant) or
with damping (enter a high time constant). Damping acts on the measuring signal
before the switch status changes, and consequently before switch-on or switch-off
delay is activated. The purpose of damping, therefore, is to prevent the status
output changing state continuously in response to fluctuations in flow.
User input:
fixed-point number 0.00 to 100.00 s
Factory setting:
0.00 s
Function description
OUTPUTS PULSE/FREQUENCY OUTPUT 1 CONFIGURATION (STATUS)
0
-4
-10
4
10
Q
t
➀➁