DEPOLOX
®
Pool Functions
WT.050.570.000.DE.IM.0714 115
2.6
Ymin
Significance Dosing rate basic load
Display Percent (%)
Explanation The parameter Ymin only applies for
Dosing pumps 2P
Pulse pumps 2P
Controllers with mA output
A basic dosing rate is output to the dosing equipment with Ymin.
Setting range The parameter Ymin can be set from 0 ... 100 %.
NOTE
The control range is limited with the parameters Ymax and Ymin.
For Ymax do not select a value lower than Ymin.
With Ymin > 0 overdosing can occur.