EasyManua.ls Logo

Evoqua DEPOLOX - Relay Plug-In Card; Analog Outputs Plug-In Card; Interfaces; Display and Operating Unit

Evoqua DEPOLOX
178 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
90 WT.050.570.000.DE.IM.0714
Technical Data DEPOLOX
®
Pool
2.2
Relay plug-in card 1 x Direct plug connector for 8-fold relay plug-in card
Storage temperature: -20 ... +70 °C
Operating temperature: 0 ... +70 °C
8 x Controller outputs
Switching values
5 A, 250 V AC, 1250 VA max
5 A, 220 V DC, 150 W max
UL/CSA-rating
5 A, 1/6 HP 125, 250 V AC
5 A, 30 V DC, 30 W max
1 A, 30 V DC - 0.24 A, 125 V DC
Analog outputs plug-in
card
1 x Direct plug connector for 4-fold analog outputs card
Storage temperature: -20 ... +70 °C
Operating temperature: 0 ... +70 °C
Calibration: Pre-calibrated
4 x Outputs (freely configurable)
Output 0 / 4 ... 20 mA
Accuracy < 0.5 % FS
Load max. can be switched over 1000 Ohm / 400 Ohm
Temperature drift max. 0.2 % / 10 °C
Load monitoring
Electrically isolated up to 50 V to ground
Interfaces 1 x RS232 for direct printer control or for firmware update (not electri-
cally isolated)
1 x RS485 for connection to:
ChemWeb server
OPC Server Data Access V2.0
CMS software 2.2
SECO-S7
Electrically isolated up to 50 V to ground
1 x IRDA for remote calibration with the photometer P42 i-cal (isola-
ted)
Display and
operating unit
1 x Operating panel with 9 keys
8 x Red LEDs for indication of operating conditions
1 x Green LED for indication of the power supply
1 x Graphic display
Resolution 240 x 64 pixels
Green background illumination

Table of Contents