70 WT.050.570.000.DE.IM.0714
Operation DEPOLOX
®
Pool
1.3
1.3.5 Setting Overview - Specifications
DEPOLOX-POOL Works setting Commissioning
Cl
2
actuator
Control output Electr.Pos.w.Ym
Ty 80 s
Tp 60 s
Pulses max./min. 100
Cl
2
parameters
Setpoint 0.45 mg/l
Xp 100 %
Tn 20.0 min
Ymin 0.0 %
Ymax 100.0
Hysteresis 0.05 mg/l
min ON 10 min.
Cl
2
parameters ECO
Setpoint
ECO
0.45 mg/l
Xp
ECO
100 %
Tn
ECO
20.0 min
Circulation ECO ON 50%
Cl
2
limit values
Min setpoint 0.30 mg/l
Max setpoint 0.80 mg/l
Min 0.30 mg/l
Max 0.60 mg/l
Hysteresis 0.05 mg/l
Cl
2
measuring range
Measuring range 1.0 mg/l
Upot 250 mV
µA measuring range 100 µA
Cl
2
adaption
Tu 01min 00s
Ts 00h 10min 00s
Tu
ECO
01min 00s
Ts
ECO
00h 10min 00s
Peak chlorination
Time ---
Interval weekly
Chlorine value 1.50 mg/l
Duration 01h 00min 00s
max. delay 00h 40min 00s
Alarm/Cl-N Dos. On