Pool Installation / Commissioning
WT.050.570.000.DE.IM.0714 143
2.7
2.7.5 Connecting the Device to the Power Supply
WARNING!
Only authorised and qualified electricians are permitted to install
the device and open the housing. The device may only be taken
into operation when the housing is closed, and must be connec-
ted to protection earth. Modifications to the device which go bey-
ond those described in this manual are not permissible.
DANGER!
The device is not equipped with a mains switch and is in operation
as soon as the supply voltage is applied. When connecting sys-
tem components (e.g. devices, motors, pumps), these must be
switched off in order to prevent uncontrolled activation or any in-
correct function.
CAUTION!
To ensure safe and correct commissioning, knowledge of the operati-
on, connected electrical load, measurement signals, cable assignment
and fuse protection of the connected devices and machines and the re-
levant safety regulations is required.
Commissioning of the device may therefore only be performed by qua-
lified and authorised electricians.
Incorrectly connected devices can be damaged, possibly irreparably, or
cause faults in other equipment when switched on or in operation.
Ensure that the measuring and control cables are not confused or
make contact with one another. Never connect or disconnect any ca-
bles to which voltage is applied!
NOTE
When installed at 230 V or 115 V:
Install a 6 A fuse in the power supply.
Recommendation: We recommend providing an on/off facility for the
device at the installation site.
Connect the system components in accordance with the following ap-
plication-related terminal diagrams.
Checking the mains vol-
tage
The device is supplied in two different versions depending on order
specifications:
24 V DC
200...240 V AC, 50-60 Hz,
can be switched to 100...120 V AC, 50-60 Hz