DEPOLOX
®
Pool Operation
WT.050.570.000.DE.IM.0714 33
1.3
Escape
Cancel the entry without saving the new value.
Move up one menu level.
Acknowledge
Acknowledge alarm message
Set the running delays to zero.
Delete adaption error.
Acknowledge max. dosing time to reactivate dosing.
1.3.2 Notes on Operation
During operation observe the following points:
Check your entry and modifications before exiting the menu.
Only press the keys with your fingers, never with hard or pointed
objects such as pencils etc. This could damage the sealed key-
pad.
Password The system runs with up to two passwords to ensure protection against
unauthorised or inadvertent incorrect operation:
The system password permits full access to all setting options.
The calibration password only permits access to the calibration
menu and the display of the menus.
Each password comprises a four-digit number combination.
NOTE
The password is not set at the works (four zeros).
A calibration password can only be set if a system password has
been set.
If the password protection was not activated with the "LOCK" soft-
key after entry/calibration, the system is automatically locked one
hour later.
The password can be changed after correct entry of the existing
password.