Pool Installation / Commissioning
WT.050.570.000.DE.IM.0714 129
2.7
No. Step Reference Compl.
If Cl
2
measurement is available:
16 Set the control mode 1.3.3
(Display 1.6.5)
17 Set control output for Cl
2
, if ne-
cessary set positioner running ti-
me "Ty" or "Pulses max./min"
1.3.3
(Display 1.1.1)
18 On positioner with feedback calib-
rate "Ym"
2.7.9 and 1.3.3
(Display 1.1.1)
19 Check setpoint for Cl
2
control, ad-
just if necessary
(only for Cl2 single feedback con-
trol)
1.3.3
(Display 1.1.2)
20 Adapt values for "Xp" and "Tn" to
control loop
1.3.3
(Display 1.1.2)
21 If a dosing pump is used, check
the "Tp" parameter, if necessary
adapt to pump
1.3.3
(Display 1.1.2)
22 If ECONOMIC operating mode
available, check "Cl
2
-parameter
ECO", adjust if necessary
1.3.3
(Display 1.1.3)
23 Check limit values for Cl
2
("Min"
and "Max"), adjust if necessary
1.3.3
(Display 1.1.4)
24
For CEDOX:
Check Min setpoint and Max set-
point,
adjust if necessary
(Display 1.1.4)
25 Check measuring range for Cl
2
,
adjust if necessary
1.3.3
(Display 1.1.5)
26
Set peak chlorination parameters
if necessary
(Display 1.1.7)