Installation / Commissioning DEPOLOX
®
Pool
146 WT.050.570.000.DE.IM.0714
2. Set the selected application 1, 2, 3 or 4 in the graphic display:
Restart the system starting from the basic display with the "Se-
lect" and the "System" menus with the "Reset" menu item and
finally "System Restart" "yes".
"RESET CPU" and then "DEPOLOX POOL" appears.
In the following display "Analog Scan" press both keys
"left" and "right" at the same time for at least two seconds.
Select the "APPLIC" function.
The "Application Select" menu then appears.
Fig. 45
With the "ENTER" function select the set application.
With the keys "up" or "down" another application (system x ty-
pe: xxxx) can be set.
To programme the set application select "ENTER". Select
"BACK" to return to the basic display.
3. Enter the employed dosing devices with the menu.
4. Check the specific customer values and enter into the menu if ne-
cessary.
5. Define the inputs and outputs in the menu.
6. Calibrate the sensors. Re-calibrate the next day, as new sensors
can change within the first 24 hours.
7. After one day adaption can be performed in the system in order to
obtain an initial parameter setting for free chlorine control