Installation / Commissioning DEPOLOX
®
Pool
148 WT.050.570.000.DE.IM.0714
NOTE
There must be distance of at least 60 % of the total path between the
set 0 % position and the 100 % position.
7. To save select "ENTER".
8. Check the position in a second operation:
Select the "MANUAL" operating mode.
Enter different values in succession for the parameter "Cl
2
" and
check the control.
If necessary repeat correction at 0 % and 100 %.
9. Determine the running time of the positioner from 0 % to 100 %.
10. Enter the determined running time in the window "Cl
2
actuator" un-
der Ty.