DEPOLOX
®
Pool Operation
WT.050.570.000.DE.IM.0714 53
1.3
Conductivity settings
(menu 1.5)
Basic display Refer to main menu
Menu select Display of all available menus
Menu conductivity Display of all available conductivity settings
Conductivity actuator
Control output 
Control direct. direct/ invers
Pulses max./min 100 / 120
Conductivity parameters
Setpoint within measuring range
Xp 0001 ... 1000 %
Tp 010 ... 180 s
Ymin 000.0 ... 100.0 %
Ymax 000.0 ... 100.0 %
Conductivity limit values
Min within measuring range
Max within measuring range
Hysteresis 0.0 ... 2.5 mS/cm
Conductivity
measuring range
Meas.Range 2500 µS/cm
10.0 / 20.0 / 50.0 / 100.0 / 200.0 mS/cm
display NaCl in g/l /NaCl in % / TDS in g/l / Off
TDS factor whenTDS display is active)
Refer. Temp. Reference temperature
of the displayed conductivity
NaCl in g/l or NaCl in %
Depiction of the sodium chloride content in g/l or in % determined
based on the conductance value of the sample water. In addition to
sodium chloride (salt), water contains other conductive substances as
well, which are also included in the calculation. The zero display only
serves to indicate the determined approximate sodium chloride
content
.
TDS:
TDS = Total Dissolved Solids
The TDS factor depends on the composition of the measured water
and has to be evaluated for each type of water.
Dosing pump 2P
Pulse pump 2P
Analog output.2P