56 WT.050.570.000.DE.IM.0714
Operation DEPOLOX
®
Pool
1.3
Explanation of system
settings
1)
Measure.filter The measurement filter serves to compensate measurement value
fluctuations in the event of irregular measurement value signals.
2)
Feed delay The feed delay delays dosing start when the device is switched on and
when the operating mode has been changed. Running of the selected
time can be cancelled with the "Acknowledge" key.
3)
Overfeed delay The maximum dosing time determines how long all control outputs run
at a 100 % dosing capacity in both manual and automatic mode. The
respective controller output is switched off after this time. When the set-
ting is "00:00:00" this function is switched off.
4)
Samp.water delay The sample water delay (DI 1) determines the time after which dosing
is deactivated, e.g. in the event of sample water stop. DI 1 flashes while
the delay time is running.
5)
System restart When the applications are changed the device must be restarted with
System Restart.
6)
Delete diagram The saved values of the past 7 days are deleted.
7)
Standard values Customer settings are deleted (except for the selected application), the
system is reset to the works settings. The sensors must be recalibra-
ted.
8)
Delete dos.avg The average dosing values from display 1.8.3 are reset to zero.
9)
Control modes Refer to chapter 1.2.5