A Diagnostic messages
228 Festo – GDCP-CMMS/D-FW-EN – 1404NH – English
Error group 64 DeviceNet error
No. ReactionMessageCode
64-2 7582h DeviceNet communication error PS off
Cause – Rec eive buffer overflow.
– Too many messages received within a shor t period.
Action • Reduce the scan rate.
64-3 7582h DeviceNet communication error PS off
Cause – S end buffer overflow.
– Insuff icient free space on the CAN bus t o transmit messages.
Action • Increase the baud rate.
• Reduc e the number of nodes.
• Reduce the scan rate.
64-4 7582h DeviceNet communication error PS off
Cause IO-message could not be sent
Action • Check that the network is connected correctly and does not
malfunction.
64-5 7582h DeviceNet communication error PS off
Cause Bus off.
Action • Check that the network is connected correctly and does not
malfunction.
64-6 7582h DeviceNet communication error PS off
Cause Overflow in the CAN controller.
Action • Increase the baud rate.
• Reduc e the number of nodes.
• Reduce the scan rate.
Error group 65 DeviceNet error
No. Code Message Reaction
65-0 7584h DeviceNet general er r or configurable
Cause – Communication is ac tivated, even though no interface is
plugged in.
– The DeviceNet interfac e is attempting to read an unknown ob-
ject.
– Unknown DeviceNet error.
Action • Check whether the DeviceNet interfac e is plugged in correctly.
• Check that the network is connected correctly and does not
malfunction.
65-1 7582h DeviceNet communication error configurable
Cause I/O connection timeout.
No I/O message received within the expected time.
Action • Plea se contact Tech nical Support.