STEP 4 - Inverter country standard and Input configuration
• Country standard (selection of grid standard):
Set the grid standard of the country in which the inverter
is installed.
• Input mode:
Only Independent configuration are available.
• Confirm the settings by clicking “END”; the inverter will
reboot.
NOTE – D After the grid standard is set you have 24 hours to make any changes to the grid
standard value; 24 hours later the Country Standard will be locked. In case of subsequent
needs of change of grid standard, the remaining time shall be reset in order to have the
24 hours of unlocked operation available again (refer to “USER menu” and “SERVICE
TOOLS menu” sections of Web UI to know how to unlock the Country Standard).
• A notification will confirm that the wizard is completed.
•
After the wizard procedure is completed, the inverter changes the behaviour of the “Power” and
“Alarm” LEDs (08), in relation of the input voltage value:
Input voltage LED Status Description
Vin < Vstart
Power = Flashing
Alarm = OFF
The input voltage is not sufficient to enable
connection to the grid.
Vin > Vstart
Power = Flashing
Alarm = ON
The input voltage is sufficient to enable connection
to the grid: the inverter waits for the grid voltage to
be present to make the connection to the grid.
•
Depending of the supply source used to complete the installation wizard steps, close the disconnect