FIMER_PVS-175-TL A.1 Version_Product manual_EN_RevC-
F
138
WARNING – B Some inverter parts may be subject to hazardous voltages for the operator.
Before performing any work on the inverter, follow this procedure for safely isolate the
inverter.
WARNING – B Important note: It is important to remark the presence of auxiliary power
supply connected to the AC grid. The inverter is supplied either by DC and AC power, so
that the internal voltages are present even in case the DC switches (19) are open.
HOT SURFACE – C When the device has just been switched off, it may have hot parts as
a result of overheating of the heated components (e.g.: transformers, accumulators,
coils, etc.) so be careful where you touch.
1. PRELIMINARY CHECKS
Weather conditions:
It is of paramount importance to evaluate the weather conditions in the risk assessment prior any
intervention on the equipment. This procedure can be applied only in case of dry environment. Don’t
proceed in case of rain (even light) or high humidity.
PPE Check: Verify the integrity of the PPE that is going to be used to perform the operations.
Equipment check:
Check the voltage tester is working correctly:
- Perform a general integrity check of the instrument; examine the test terminals, its integrity and
make sure they are properly fixed; make sure the batteries level is enough high (don’t use the
instrument in case the message “LOW BATTERY” is present) or replace them.
- Perform test of the instrument using an energized AC socket and a DC voltage source (example:
battery in the service car) with known voltage level; in case the instrument is provided with a self-
test feature, follow the instructions provided in the instrument manual to carry out the self-test.
Check the voltage tester is working correctly:
Check the DC current probe is properly working, make sure to perform the “ZERO-OFFSET
procedure and to select suitable DC measurement range.
2. PPE
WARNING – B All the following activities (till the completion of the procedure) must be
performed wearing the PPE.
Wear the appropriate PPE for carrying out the operations (overall resistant to electric arc, dielectric
helmet with visor, insulating gloves).