Problem Possible causes Solution
The wireless board does
not communicate
correctly with the
inverter inside of which
it is installed
(inconsistency in the
detected data read by
the board), or when
working in “Access Point
Mode”, it’s not possible
to access the Web User
Interface.
The wireless board of the
inverter could be damaged.
Request a service intervention to check that
the inverter wireless board is working
correctly.
Wrong Inverter Date/Time
settings.
Check if Date/Time has correctly set on the
inverter; correct it if necessary.
Alternating difficulties in
the local connection to
the Web User Interface.
The inverter might not be
correctly powered (for
example, if the inverter is
switched off at night, the Web
User Interface cannot be
accessed).
Access to the Web User Interface only when
the inverter is correctly powered.
The wireless connection
signal between the device in
use and the router or the
Inverter, may not have
sufficient power or it may be
disturbed by obstacles which
affect the communication.
Make sure that the signal between the
wireless devices which interact with the
inverter are sufficiently high and that any
obstacles such as metal cages or walls, walls
in reinforced concrete or strong
electromagnetic fields do not affect
communication.
Although the Inverter
has been configured
correctly in “Station
Mode” and works
correctly on the local
network, no data has
been transmitted to the
Aurora Vision®.
The MAC address used to
register the inverter on the
Aurora Vision® platform is
not the same as the actual
address associated with the
inverter.
Make sure that the MAC address registered
on the Aurora Vision® platform is actually the
one associated with the inverter. If it is not,
modify the registered MAC address.
The wireless network to
which the Inverter is
connected, could be
protected by a Firewall which
prevents the remote
exchange of data with the
Aurora Vision® platform.
Contact the network administrator in order to
have the Firewall configured so that the
remote exchange of data between the
Inverter and the Aurora Vision® platform is
allowed.