Chapter 5 Function Code
F33 to
F35
Pulse Output [FMP] (Pulse rate, Gain to output voltage, Function)
These function codes allow terminal [FMP] to output monitored data such as the output frequency and the
output current in a variable rate pulse train or a fixed rate pulse train. The fixed rate pulse train (whose pulse
duty control produces a variance of an average output voltage of the pulse train) can be used to drive an
analog meter.
The output pulse can be specified for each of monitored data items.
To use the terminal [FMP] for pulse train output, set F33 to an appropriate value and set F34 to "0."
To use the terminal for average voltage output, set F34 within the range from 1% to 300%. This setting
disables the setting of F33.
Table 5.4-39
[FMP] output form Data for F33 Data for F34 Pulse duty Pulse rate
Pulse output 25 to 6000 p/s 0 Around 50% Variable
Average voltage - 1 to 300% Variable 2000 p/s
Pulse rate (F33)
F33 specifies the pulse rate at which the output of the monitored item selected reaches 100%, in accordance
with the specifications of the counter to be connected.
y Data setting range: 25 to 6000 (p/s)
Gain to output voltage (F34)
F34 allows you to adjust the output voltage (average voltage) within the range of 0 to 300 (%).
Pulse output waveform FMP output circuit
Figure 5.4-33
Figure 5.4-34
Function (F35)
F35 specifies what is output to the output terminal [FMP]. Those contents are the same as those for function
code F31. Refer to the table in the description of F31.