A-38
App. G Replacement Information
FRENIC5000G9S FRENIC-MEGA
Default
setting
Default
setting
Code Name Data setting range
22 kW or
below/30 kW
or above
Code Name Data setting range
22 kW or
below/30 kW
or above
06 Deceleration Time 1 0.00: Coast-to-stop F08 Deceleration Time 1 0.00
0.01 to 3600 s
6.0/20.0
0.01 to 6000 s
6.00/20.00
07 Torque Boost 1 0.0:
Auto torque boost
F37 Load Selection/Auto Torque Boost/
Auto Energy Saving Operation 1
2: Auto torque boost 1
0.1 to 0.9:
Square law reduction torque
F37 Load Selection/Auto Torque Boost/
Auto Energy Saving Operation 1
0: Variable torque load 1
F09 Torque Boost 1 0.0 to 20.0: * Depending
on inverter
capacity
1.0 to 1.9:
Proportional torque
2.0 to 20.0:
Constant torque load
F37 Load Selection/Auto Torque Boost/
Auto Energy Saving Operation 1
1: Constant torque load 1
F09 Torque Boost 1 0.0 to 20.0: * Depending
on inverter
capacity
0.0:
Auto torque boost
F37 Load Selection/Auto Torque Boost/
Auto Energy Saving Operation 1
5: Auto energy saving (Auto torque boost during
ACC/DEC)
1
0.1 to 0.9:
Square law reduction torque
F37 Load Selection/Auto Torque Boost/
Auto Energy Saving Operation 1
3: Auto energy saving (Variable torque load
during ACC/DEC)
1
F09 Torque Boost 1 0.0 to 20.0: * Depending
on inverter
capacity
1.0 to 1.9:
Proportional torque
2.0 to 20.0:
Constant torque load
F37 Load Selection/Auto Torque Boost/
Auto Energy Saving Operation 1
4: Auto energy saving (Constant torque load
during ACC/DEC)
1
F09 Torque Boost 1 0.0 to 20.0: * Depending
on inverter
capacity
08
Electronic Thermal
Overload Protection
for Motor
(Mode
selection)
0: Disable F11 Electronic thermal 1 (operation
level)
0.00: Disable Motor
rated current
1: Enable (for general-purpose motor) F10 Electronic thermal 1 (mode
selection)
1: For a general-purpose motor with
shaft-driven cooling fan
2: Enable (for inverter motor)
1
2: Enable
(For an inverter (FV) motor with separately
powered cooling fan)
1
09 (Operation
level)
20% to 105% of the rated current of the inverter 100% of
motor rated
current
F11 (Operation level) 1% to 135% of the rated current (0.01 to 2000) of
the inverter
Motor
rated current
75 = 1
when the
auto-energy
saving
operation is
active
75 = 0
when the
auto-energy
saving
operation is
inactive
(2/12)