Chapter 6. Communication
156 AquaTrans™ AT600 User’s Manual
Command 225 (0xE1): Read Signal Setup
This command is to read flow meter signal setup.
Table 158: Request Data Bytes for Read Signal Setup
Byte Format Description
0 Unsigned-8 signal setup type:
1. Delta T Offset
2. Percentage Peak
3. Min Peak Percentage
4. Max Peak Percentage
Table 159: Response Data Bytes for Read Signal Setup
Byte Format Description
0 Unsigned-8 signal setup type:
1. Delta T Offset
2. Percentage Peak
3. Min Peak Percentage
4. Max Peak Percentage
1 - 4 Float signal setup Value
Table 160: Command-Specific Response Codes for Read Signal Setup
Code Class Description
0 Success No Command-Specific Errors
1Undefined
2 Error Invalid Selection
3-4 Undefined
5Error Too Few Data Bytes Received
6 Error Device-Specific Command Error
7-127 Undefined