AT600 User’s Manual 79
Chapter 5. Communication
706 1798 RO System Flow error Bitmap RO INT32
708 1800 RO System Device error Bitmap RO INT32
70A 1802 RO System Warning Bitmap RO INT32
740 740 1856 RO System Protocol type RO INT32
900 900 2304 Viewer Display Language RW INT32
902 2306 User Display Backlight Enable RW INT32
904 2308 User Display Timeout RW INT32
906 2310 Viewer Display Type RW INT32
908 2312 Viewer Display Variable1 Type RW INT32
90A 2314 Viewer Display Variable2 Type RW INT32
90C 2316 Viewer Display Totalizer1 Type RW INT32
90E 2318 Viewer Display Totalizer2 Type RW INT32
910 2320 Viewer Display Decimal selection RW INT32
940 940 2368 User select the velocity RW INT32
942 2370 User select the Actual Volumetric RW INT32
944 2372 User
select the Standardized
Volumetric RW INT32
946 2374 User select Mass RW INT32
948 2376 User select Totalizer RW INT32
A00 A00 2560 RO Display Variable1 Value RO (IEEE 32 bit)
A02 2562 RO Display Variable2 Value RO (IEEE 32 bit)
A04 2564 RO Display Totalizer1 Value RO (IEEE 32 bit)
A06 2566 RO Display Totalizer2 Value RO (IEEE 32 bit)
C00 C00 3072 User
Analog Out Error Handling
Value RW (IEEE 32 bit)
C02 3074 User
Analog Out Test Value
(Percent of Span) RW (IEEE 32 bit)
C04 3076 User Analog Out Zero Value RW (IEEE 32 bit)
C06 3078 User Analog Out Span Value RW (IEEE 32 bit)
C08 3080 User Analog Out Base Value RW (IEEE 32 bit)
C0A 3082 User Analog Out Full Value RW (IEEE 32 bit)
C40 C40 3136 User Digital Out 1 Pulse Value RW (IEEE 32 bit)
C42 3138 User
Digital Out 1 Frequency Base
Value RW (IEEE 32 bit)
C44 3140 User
Digital Out 1 Frequency Full
Value RW (IEEE 32 bit)
Table 5: MODBUS Map (cont.)
Register
(in Hex)
Register (in
Decimal) Access Level Description RO/RW Format