AT600 User’s Manual 47
Chapter 3. Initial Setup and Programming
3.6.2c Setting the Frequency
Setting Measurement Type
Setting Base Value/Full Value/Frequency
Frequency sends out a continuous square wave, with the frequency proportional
to a measured value. Select
Frequency and press []. The following screen
appears.
Select
Measurement and press []. A screen similar to the following appears.
In the Measurement menu, select the type of analog output to be used, and press
[]. The screen returns to the previous display.
The Base Value is the measurement value represented by 0 Hz. The Full Value is
the measurement value represented by Full Frequency. The Full Frequency is
the maximum Hz, which represents the Full Value of measurement.
Use the [] or [] arrow keys to select the appropriate option and press
[]. A
screen similar to the following appears.
Note: The operation steps of Base Value, Full Value and Full Frequency are
the same.
To change the existing number, press
[] and a screen similar to the following
appears.
Note: The units that appear will be the units selected in Units Setting on page
28.
Digital Output B
Off
Pulse
Frequency
Alarm
Frequency
Measurement
Base Value
Full Value
Full Frequency
Measurement
Velocity
Act Volumetric
Std Volumetric
Mass
Frequency
Measurement
Base Value
Full Value
Full Frequency
Base Value
Base Value
0.0000 m/s