Cell  Text  Status  Description 
000D  Ctrl Status  READ  Binary word used to indicate the status of control data 
000E  Grp now  READ  Indicates the active setting group 
000F  LSB Stage  READ  Indicates the last received load shedding command 
0011  Software   READ  Software reference for the product 
0020  Log Status  READ  Indicates the current status of all the logic inputs 
0021  Rly Status  READ  Indicates the current status of the output relay drives 
0022  Alarms  READ  Indicates the current state of internal alarms 
0  Uncfg  READ  Error in factory configuration settings 
1  Uncalib  READ  Operating in uncalibrated state 
2  Setting  READ  Error detected in stored settings 
3  No Service  READ  Out-of-service and not functioning 
4  No Samples  READ  No A/D samples but still in service 
5  No Fourier  READ  Fourier is not being performed 
6  Test Wdog   SET  Test watchdog by setting this bit to “1”; 0 = normal 
0002 SYS Password [PWP] 
The selected configuration of the relay is locked under this password and cannot be 
changed until it has been entered.  Provision has been made for the user to change the 
password, which may consist of four upper case letters in any combination.  In the event 
of the password becoming lost a recovery password can be obtained on request, but the 
request must be accompanied by a note of the model and serial number of the relay. 
0003 SYS Function Links [PWP] 
These function links enable selection to be made from the system options. 
0004 SYS Description [PWP] 
This is text that describes the relay type.  It is password protected and can be changed by 
the user to a name which may describe the scheme configuration of the relay if the relay 
is changed from the factory configuration. 
0005 SYS Plant Reference [PWP] 
The plant reference can be entered by the user, but is limited to 16 characters.  
This reference is used to identify the primary plant with which the relay is associated. 
0006 SYS Model Number [READ] 
The model number that is entered during manufacture has encoded into it the mechanical 
assembly, ratings and configuration of the relay.  It is printed on the frontplate and should 
be quoted in any correspondence concerning the product. 
0008 SYS Serial Number [READ] 
The serial number is the relay identity and encodes also the year of manufacture.  
It cannot be changed from the menu. 
0009 SYS Frequency [SET] 
The set frequency from which the relay starts tracking on power-up. 
000A  Communication Level [READ] 
This cell will contain the communication level that the relay will support.  It is used by 
master station programs to decide what type of commands to send to the relay. 
000B SYS Relay Address [SET]