5.2.3 Controlled change of setting group
Link SD4 must be set to “1” to make the second setting group active. Now energising a
logic input allocated in mask [070A STG GRP2] will select setting group 2.
The logic input could be energised via the contacts of one of the output relays so that
change of setting group will be in response to some control or supervision functions.
5.3 Initial factory settings
As received the relay will be configured with the settings shown below. The password
must first be entered before the configuration settings on the relay can be changed either
via keypad or over the serial communications port.
5.3.1 System data settings
F E D C B A 9 8 7 6 5 4 3 2 1 0
SYS Password AAAA
SYS Function Links 0 0 0 0 0 0 1 0 0 0 0 1 0 1 1 0
SYS Description KVGC202 01Fx 1Gx
SYS Plant Ref. KVGC202 01Fx 1Gx
SYS Model No. KVGC202 01Fx 1Gx
SYS Frequency 50 Hz
SYS Relay Address 255
Alarms x x x x x x x x x 1 0 0 0 0 0 0
5.3.2 Link settings
F E D C B A 9 8 7 6 5 4 3 2 1 0
CTL Links 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
LOG Links 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0
5.3.3 Initial control settings
Control Symbol Factory Settings
CT Ratio 1:1
VT Ratio 1:1
Rated current
In
1A
Regulated voltage Vs 110V
Dead band dVs ±1%
Circulating current compensation
Vc (volt/
In)
0
Resistive LDC compensation
Vr (volt/
In)
0
Reactive LDC compensation (= reverse)
Vx (volt/
In)
0
Low power factor LDC compensation Angle Vr/Vx
Initial definite time delay tINIT DT 30 seconds
Inter tap delay tINTER 5 seconds
Tap pulse duration tPULSE 1 second
LSB Level 1 0
LSB Level 2 0
LSB Level 3 0
Tap change indication time tTapchange 1 second